Winters here settle the question before cost does. The average overnight low across December, January and February is 12°F, and a standard heat pump starts losing ground well before temperatures get that low. Its heat output falls short of the rating once it's below 40°F outside, and below about 35°F it typically needs backup heat to make up the difference. Both marks sit well above 12°F, and every one of the roughly 160 nights a year that hit freezing or below here is colder than both.
That's over half the nights in the eight months your heat runs, October through May. On about 25 of those nights a year, it gets down to 0°F or colder. A standard heat pump keeps running at those temperatures, but on backup heat for a good part of it, usually electric resistance coils, which cost more to run than the compressor itself.
A cold climate heat pump changes that math. To earn the ENERGY STAR Cold Climate label, it has to deliver at least 1.75 units of heat per unit of electricity at 5°F and hold onto at least 70 percent of its 47°F capacity at that same temperature, tested by a third party rather than claimed by the manufacturer. Field tests of prototype cold climate units in occupied homes back this up: backup heat covered only a small share of the load between 0°F and 35°F, and the unit running on backup alone was rare even above 0°F. If a heat pump is the direction you're leaning, this is the spec that matters here, not the base federal minimum.